Free Fire Door Inspection Checklist (UK) — PDF & Excel
Gaps, seals, closers, hinges — the item-by-item check, plus the quarterly and annual regime for residential buildings over 11m.
Since the Fire Safety (England) Regulations 2022, responsible persons in residential buildings over 11m must check fire doors in common parts quarterly and flat entrance doors annually. Every other premises still needs its fire doors maintained under the Fire Safety Order. This checklist covers both.
⬇ Download PDF (print-ready)⬇ Download Excel (editable)
Free for use within your organisation. No sign-up required.
What the checklist covers
- Gaps ~3–4mm at head and sides
- Intumescent strips and smoke seals intact
- Closer shuts the door fully onto the latch from any position
- Three secure, marked hinges; intact glazing; correct signage
- The classics: no wedges, no disconnected closers
How to use it
One line per door per inspection; defects go straight to the rectification sheet with a named owner. Full legal picture: fire door inspection logbooks.